| Measure Range |
Range 1 : 0 - 1 ACA Range 2 : 0 - 5 ACA * Isolated |
| Output |
4 - 20 mA |
Range 1 : 0 ACA = 4 mA , 0.5 ACA = 12 mA , 1 ACA = 20 mA Range 2 : 0 ACA = 4 mA , 2.5 ACA = 12 mA , 5 ACA = 20 mA |
| External Adjustment |
ZERO VR , SPAN VR |
| Power Supply |
90 - 260 ACV/ 50 Hz/60 Hz |
| Operation Temperature |
0 - 50 ℃ ( 32 - 122 ℉) |
| Operation Humidity |
Less than 80 %RH |
| Accessory Included |
None |
| Optional Accessories |
Current transformers : CT 50/5A , CT 100/5A , CT 1000/5A |
| Mounting |
Din rail or Wall |
| Case |
ABS plastic |
| Others |
Two wires input, 6 Amp fuse |